29
4 Output 1 Percent o1uL 0 to 100 percent
100
Upper Limit
(o1uLand o1LL will
not be seen if out1 = 0,1,2)
5 Output 1 Percent o1LL 0 to 100 percent
0
Lower Limit
6 Output 2 out2 0 = None (Position
0
Proportioning - Direct Closed)
1=On-Off- Direct
2=On-Off- Reverse
3=Time Proportioning- Direct
4=Time Proportioning-Reverse
5=Current Proportioning- Direct
6=Current Proportioning -Reverse
7=Position Proportioning
(Reverse/Closed)
7 Output 2 Percent o2uL 0 to 100 percent
100
Upper Limit (o2uL and
o2LL will not been seen if
out2 = 0,1,2,7)
8 Output 2 Percent o2LL 0 to 100 percent
0
Lower Limit
9 Alarm 1 AL1 0 to 6
0
the Alarm Point 0 = None
is selected in the 1=Process Alarm-Direct
Tune mode 2=Process Alarm-Reverse
3=Deviation Alarm-Direct
4=Deviation Alarm-Reverse
5=Deviation Band Alarm-Open within band
6=Deviation Band Alarm-Closed within band
10 Alarm 2 AL2 Same selections as Alarm 1
0
11 Display Select diSP 1=Process value only
1
2=Process value/setpoint
3=Deviation only
4=Deviation and setpoint
5=Setpoint only
12 Decimal Position dPoS 0 to 3
0
0=None
1=One decimal place
2=Two decimal places
3=Three decimal places
RTD and thermocouple inputs
are limited to either 0 or1 decimal positions
13 Engineering Units Euu -9999 to 9999
1000
Upper Value (Euu and
EuL will be seen if the pen
input select = 30,31,32,33,34)
14 Engineering Units EuL -9999 to 9999
0
Lower Value
15 Hysteresis for HyCo 0 to 300
3
Control Outputs Width of Hysteresis Band
(See page 66 for definition)
DISPLAY AVAILABLE FACTORY YOUR
STEP DESCRIPTION CODES SETTINGS SETTING SETTING